Construction |
| Core
Material |
: |
FRP Rod |
| Polymer
Material |
: |
Silicone
Rubber compound |
| Method of
Manufacture |
: |
Direct
Moulding of Solicone Rubber over FRP rod |
| Metal end
fittings |
: |
M.C.I |
Method of
connecting
Metal Fitting with FRP rod |
: |
Crimping |
|
|
Specification |
| Railway
Standard |
: |
TI/SPC/OHE/INSCOM/0990
Issued by Research Designs and
Standards Organisation, Ministry of Railways, India. |
|
International Standard |
: |
IEC:
61109-1992 |
|
|
Electrical
Characteristics |
| Dry
lighting impulse with-stand Voltage |
: |
240kvp for
positive Polarity
260kvp for Negative Polarity |
| Wet power
frequency with-stand Voltage |
: |
Vertical
Mounting : 100kV (rms)
Horizontal Mounting : 125kV (rms) |
|
|
Mechanical
Characteristic |
| Minimum
failing tensile load |
: |
9900kgf |
| Minimum
failing bending moment |
: |
210kg.m. |
|
|
Profile Parameters |
The profile
parameters of these insulators meet the requirements of
IEC:815. |
|
Specific Creepage
Distance |
16mm/kV for
standard (Normal) zone
20mm/kV for Polluted zone |
|
Guaranteed
Creepage Distance |
850mm (Min) for
Standard (Normal) zone
1050mm (Min) for Polluted Zone |
|
Dimensions |
As per Railway Standard.
Inter changeable with existing Ceramic Insulators |